Showing all 4 results

View
  • 758-1

    ,

    Interactive Fire Control Panel IFS7002 – four signal loops

    Mains:
    Back up batteries
    – Battery type: lead, gel electrolyte
    – Number of batteries: 2 pcs
    – Connection: serial connection
    – Nominal voltage of the back up battery: 2 х 12V
    – Nominal capacity C20: 18 Ah
    – Charge voltage: 28,2V
    Power supply to external devices
    – Voltage: (24±5)V
    – Maximum current value (including current of monitored outputs and power loop): 5А
    Dimensions: 493x464x110mm
    Weight (batteries not included): 10kg

  • 758

    ,

    Interactive Fire Control Panel IFS7002 – four signal loops

    Mains:
    Back up batteries
    – Battery type: lead, gel electrolyte
    – Number of batteries: 2 pcs
    – Connection: serial connection
    – Nominal voltage of the back up battery: 2 х 12V
    – Nominal capacity C20: 18 Ah
    – Charge voltage: 28,2V
    Power supply to external devices
    – Voltage: (24±5)V
    – Maximum current value (including current of monitored outputs and power loop): 5А
    Dimensions: 493x464x110mm
    Weight (batteries not included): 10kg

  • 178

    ,

    Interactive Fire Control Panel IFS7002 – two signal loops

    Technical data

    Fire alarm loops
    – signal: 2
    – power: 1

    Addressable devices in one signal loop: Up to 125
    Cross section of the signal loop wire: (0.8-2.5) mm2
    Maximum resistance of the signal loop: 100Ω
    Number of devices in one branch: Up to 32
    Fire alarm zones: Up to 250
    Addressable devices in one zone: Up to 60
    Response time to activated detector signal: Up to 10 seconds
    Registered events by the counter of fire events: Up to 9999
    Archive of events: Op to 1023

    Power supply:
    – mains: 220/230VAC, 50/60Hz
    – backup batteries: 2×12 VDC, 18Ah

    Current consumption of power supply loop: Up to 1A

    Outputs:
    – relay 30VDC/1A: 3
    – controllable 28V DC/1A: 2
    – auxiliary supply 24VDC/1A: 1

    Interfaces:
    – RS 232 or RS 485: 1
    – CAN: 2

    Dimensions: 480 x 445 x 100 mm
    Weight (batteries not included): 7.1 kg
    Operating temperature: Minus 5oC to 40oC
    Relative humidity: (93±3) % at 40oC
    Degree of protection: IP 40

  • 1047-600x467

    ,

    Interactive Fire Control Panel IFS7002 – one signal loop

    Performance:
    – Control over fire alarm loops and monitored outputs for fault conditions (short circuit and interruption) and automatic reset.
    – Detection of removed devices in the loops and automatic reset.
    – Ability to set the zones in Coincidence Mode.
    – Two phases of Fire condition, programmable time for Fire condition stage I, separately for each zone.
    – Option to prolong the time period for Fire condition stage I with programmable inspection period, specified for each zone.
    – Built-in sounder for fire condition – one tonal, discontinuous, can be switched off.
    – Built-in sounder for fault condition – one tonal, discontinuous, can be switched off.
    – Built-in real time clock.
    – Set of test modes and options for adjustment:
    • Setting the clock;
    • Check ups on light and sound indications;
    • Test of fire alarm zones;
    • Adjustment of outputs and integrated external devices;
    • Programming of parameters and modes of operation;
    • Remote programming of the parameters from distant operator control point.
    – Energy independent archive of registered events with the events type, date and hour – up to 1023 events.
    – Interfaces for communication with external devices – CAN 2.0B and RS-232 (directly or via modem).

    Indications of registered events:
    – Light indication: LED
    – Text messages: LCD display, 320×240 points, backing
    – Sound signaling: built-in sounder

    Power supply:
    Mains
    – Voltage: 220/230 V
    – Frequency: 50 Hz
    Back up batteries
    – Battery type: lead, gel electrolyte
    – Number of batteries: 2 pcs
    – Connection: Serial connection
    – Nominal voltage of the back up battery: 2 x 12V DC
    – Nominal capacity C20: 5 Ah
    – Charge voltage: 28V
    Consumption on back up batteries supply
    – At 24V: < 160 mA
    – At 26V: < 150 mA
    Power supply to external devices
    – Voltage: (24±5)V
    – Maximum current value (including current of monitored outputs): 1A
    Dimension: 286x148x125 mm
    Weight (batteries not included): 2,2 kg